- Before
- Works four jobs a day across 11 kV substations, opening cable boxes and switchgear with the open work order and little else. Wants to know what has been done to a unit before opening it.
- Now
- Scans the tag and gets the asset's life story. It shows the repeat, the crew note that named the fix, the parts and the hazards, each line with its record. Speaks the closeout and signs it.
A ring main unit trips three summers running, and its service history shows why
The utility runs electricity and water networks. One 11 kV ring main unit at a secondary substation has tripped on earth fault on Way 2 three summers running. Each time, the 312 customers on its ring lose supply. A high-voltage field technician is sent to investigate. Here is the day, screen by screen, in the working solution.
A worked example on sample data. Names, IDs and figures on the screens and in this section come from the demo.
- 0106:00
Four jobs, each history read before the van leaves
DispatcherThe dispatcher builds the technician's route. It covers the ring main unit at 08:30, a transformer at 13:45, a low-voltage pillar at 15:00 and a second ring main unit at 16:15. Each job's history is read by 06:00 and cached on the tablet. The van list is built from the parts each past job used or named. The termination kit is loaded. The 63 mm gland, breather and heater for the ring main unit are at the depot. So are a gasket kit for the transformer and anti-tamper bolts for the pillar.
“Bushing gasket kit, 200 kVA · the transformer · named in a past note, not yet ordered”
- 0208:30
The technician scans the tag on the switchgear
HV field technicianAt the secondary substation, the technician points the tablet at the tag. It reads the unit's ID and matches it to one asset in the register. The match includes the ID the unit carried before the system change. Today's job, raised by the asset engineer, reads “Investigate repeat earth fault, Way 2 cable box”. A planned outage runs from 09:00 to 13:00.
Tag and asset resolver: if two assets could match, it asks instead of guessing.
- 037.0 seconds later
Seventeen years on one timeline
History reader · Pattern finderThe life story comes back, from commissioning to today. It holds 19 events from 14 records and 23 photos. They sit in five lanes: installs and jobs, faults, repairs, tests and inspections, and parts. One inspection found the ground around the plinth wet. A partial-discharge survey heard 14 dB ultrasonic at the Way 2 cable box and said “Monitor, resurvey in 12 months.” It was not resurveyed. The pattern finder joins the three faults with a red band.
“Repeat found: 3 earth-fault trips · each one between June and August · all on the Way 2 cable box”. They came 383 and 343 days apart, with 148,200 customer minutes lost.
- 04One switch
Fold by season, and the summers line up
Pattern finderFold by season redraws the timeline as years stacked over a single January-to-December line. The three trips, two in July and one in August, fall in the same summer column. A work-order list does not show this. It is the view that turns three call-outs into one pattern.
“all 3 trips fall here”
- 05After the first trip, as written
The crew that found the cause wrote it down
Crew lead, since retiredAfter the first trip, the crew re-terminated the Way 2 red phase and found the gland split. The record opens as it was written, with the quoted passage highlighted. It shows the crew, the times, the fault code and the photos of the split gland and the tracking. The follow-up job was cancelled as “merged with planned maintenance”. Since then, crews have dried the box and reset it.
“Gland on the Way 2 cable box is split and water is getting in round the cable. Box wet inside, tracking on the red phase. Replace the cable box gland and fit a new breather. No 63 mm gland on the van.”
- 06Ranked
The likely cause, and whether the fix held elsewhere
Cause and fix advisorWater through the split Way 2 gland ranks High, on 5 records. A dead anti-condensation heater, found between the first and second trips, ranks Medium. Termination workmanship ranks Low. Way 2 was re-terminated after the first trip and tripped again 383 days later. The technician asks whether the gland and heater fix worked on other units of the same model. Nine had a wet cable box, and all nine had the same gland and heater fitted. None has tripped since, over at least 24 months each.
“This unit is the tenth with the same story, and the only one where the gland job was cancelled.”
- 07Before the box is opened
What past crews found inside, each with its record
Cause and fix advisorPast visits recorded four hazards. At the last trip, the Way 2 cable box was wet with tracking on the red phase. The survey heard discharge at this box. SF6 gas pressure last read 1.29 bar, so the gauge must be checked before operating. Water stands at the plinth after rain. Beside the hazards are the past fixes and how long each held: 383 days, 343 days, and 87 days so far. The two fixes that were not done are listed too.
“Prove dead and earth Way 2 to the approved procedure before opening, under the job's switching schedule. Switching is by control.”
- 0808:41
The parts from the old note, reserved for approval
Parts checker · Crew leadThe gland, breather and heater are not on the van. The depot has 4, 6 and 2 of them. The technician reserves the three parts for today's job, to collect before 09:00. The crew lead approves at 08:43, and the parts are ready at the depot trade counter.
“The agent reserves. It does not order. Nothing leaves the store until the crew lead approves.”
- 0912:41
A spoken closeout becomes the record
Closeout writerThe technician speaks the closeout at the substation, in 2 min 14 s. The gland was split, as the retired crew lead's note said. A new 63 mm brass gland and breather are fitted. The heater had no supply because the auxiliary fuse had gone, so both were replaced. The termination is sound. The closeout writer drafts the cause, work done and parts fitted. It adds the readings after the fix: IR 12 GΩ at 5 kV, PD ultrasonic 0 dB, TEV 7 dB and SF6 1.30 bar. It asks for the one reading that was missing.
Asked for: “Heater current after the fix?” The technician: “Heater drawing 0.22 amps.”
- 1012:52 · Signed
The fix joins the asset's story, so the next crew knows first
HV field technicianThe technician signs the job as the person who did the work. The life story gains a new event: gland, breather and heater replaced. The old recommendation and the cancelled job are closed. The repeat is marked “fix fitted today, watch next summer”. The pattern finder checks it again once next summer is over.
Only the technician who did the work signs the closeout.