A stuck tap changer, a retired fitter's note and a fix the fleet now uses
On a set Tuesday at 06:42, SCADA at one of the sample utility's 132/33 kV primary substations raises “T2 OLTC: tap change incomplete”, then “Motor protection tripped”. The on-load tap changer on transformer T2 is at 184,212 operations, resting between taps 9 and 10. The engineer on call, two years in the job, has not met this fault before. The fitter who had met it retired last year. Here is what happens next, screen by screen, in the working solution.
A worked example on sample data. Names, IDs and figures on the screens and in this section come from the demo.
- 0106:58
The fault, in plain words
Maintenance engineer, substationsThe engineer types what is in front of them: “OLTC stuck between taps, T2, motor breaker tripped”. The open job and the 06:42 alarm are already on the question bar. The run log shows the agents at work: the tap changer manual, rev 7, read at its fault-finding, hand-operation and drive-shaft sections; 186,400 work orders and 1,240 root-cause reports searched; the safety steps locked to the substation procedure.
Manual and procedure searcher: “found a newer service bulletin: coupling wear past 150,000 operations, not in the manual's table”
- 029.4 seconds later
A six-step fix recipe, each step cited
Fix recipe writerFive agents, 8 steps, 6 documents, 14 past jobs. The answer opens with the symptoms it matched (tap change incomplete alarm, motor protection Q1 tripped, indicator between taps 9 and 10, past 150,000 operations), then six numbered steps, each with its source. Beside it, Manual says · Field says: the manual's fault table points to the motor; the field record says check the coupling first, test the motor, and leave it if it passes.
What was done, and did it hold? Coupling replaced: 0 of 9 came back. Motor replaced: 2 of 3 came back.
- 03Step 4
The retired fitter's note, in the step where it matters
Senior substation fitter, retiredStep 4 says inspect the vertical drive-shaft coupling, gearbox end first, for a sheared nylon insert or a missing shear pin. On drives of this model past 150,000 operations this is the usual cause, which is why it comes before any motor change. The retired fitter's job note from an earlier job on this same transformer is pinned to the step. The safety steps, 1 and 6, are quoted from the substation procedure and the Safety Rules, not rewritten.
Job note on this unit, four years and eight months earlier: “Replace the drive-shaft coupling, not the motor. Motor tests fine every time, it's the coupling insert shearing. Check the gearbox end first.”
- 04Why not the motor
Fourteen jobs, read from the technicians' own words
Work history minerThe work history miner read each closing note on record for this tap changer model and symptom, and grouped them by the fix actually done: coupling replaced 9 times, 0 repeats in 90 days; motor replaced 3 times, 2 repeats in 30 days. On two units the new motor was back in 9 and 11 days, and both times the next job found the coupling insert sheared. On a third the motor winding really was open circuit, so step 3 still tests the motor.
A later job, after the fitter retired: “Took two calls to find someone who knew. Coupling insert. Replaced the kit.”
- 0507:05
The right part reserved, the expensive one left on the shelf
Parts and tools checkerThe parts list shows the coupling insert kit at $110, 4 in stock at the nearest depot with its bin, and the shear pin, 12 in stock. The $6,200 drive motor is marked not needed. The engineer reserves the kit against the open job; three past jobs where this fix worked sit underneath, each done in about two hours.
Parts and tools checker: reserves only when the engineer asks, and does not order.
- 0607:40
The recipe becomes the job sheet
Maintenance engineer, with the authorized personThe authorized person issued the permit at 07:36: T2 motor drive cabinet, Q1 open, locked, notice fitted. The engineer works through the recipe as a checklist. Motor readings come in from the insulation tester (210 MΩ and 4.3 Ω), and each is checked against the manual's range as it lands. Motor good, so the motor stays.
“✓ within the manual's range” · insulation resistance > 20 MΩ, winding 4.1–4.6 Ω
- 0709:52
Back on automatic voltage control, and the note writes itself from the readings
Knowledge stewardCoupling insert sheared at the bevel gearbox end; insert and shear pin replaced, grub screws at 12 N·m, step time 5.1 s. T2 is back on REMOTE and automatic voltage control at 09:52, 2 h 12 after the job started. When the engineer closes the job, the knowledge steward drafts the closing note from the readings and finding and links it to the fitter's earlier job on this unit. The note is the engineer's to edit and sign.
Drafted note: “Second coupling failure on this unit in 4 years and 8 months: suggest a coupling check at each tap changer maintenance on units of this model past 150,000 operations.”
- 08Signed 09:58
No note reaches anyone else until a reliability engineer reads it
Reliability engineer, network assetsThe engineer signs and the note goes to Field fixes, waiting for the reliability engineer. Beside it, the knowledge steward suggests adding this job to the model's field fix as its 10th coupling job. The reliability engineer can publish the note or ask the engineer a question first, and publishes it.
“Nothing changes in an answer until a reliability engineer approves it.”
- 0914:20
Field-proven, for each unit of this model past 150,000 operations
Reliability engineerThe proposal puts the answer today, which follows the manual's table, beside the proposed recipe, with the evidence: at least 3 jobs with the same fix (9); none back within 90 days (0 of 9); consistent with the newer service bulletin; safety steps unchanged, quoted from the substation procedure. It changes the answer for 12 assets. The reliability engineer approves it as field-proven, and could instead have asked the manufacturer to confirm, or rejected it with a reason.
“Approved by the reliability engineer at 14:20. Answers now lead with this fix.”
- 10Before the next one leaves
Ask the next expert now, while they are still here
Senior process technician, water treatment worksA senior process technician retires in 66 days after 34 years on dosing, filters and pumps; 41 % of the technician's 1,412 jobs have a usable note. The coverage map shows where the knowledge is written down and where it is not: filters at 29 %. The knowledge steward drafted questions from the gaps for the next session, such as what “as before” means on 9 high-lift pump 2 vibration jobs.